Conventional Thermostat Sequence Of Operation - Trane Symbio 700 Controller Application Manual

With precedent packaged rooftop air-conditioners
Hide thumbs Also See for Symbio 700 Controller:
Table of Contents

Advertisement

Conventional Thermostat Sequence of Operation

When the Precedent system is configured to operate with a conventional thermostat, the controller
provides protection for the system (see General Support Sequence section) and continues to provide
insight to operating conditions. A conventional thermostat can be applied with CVZT and single zone
VAV configured systems. While not recommended, a conventional thermostat can be applied to single
zone variable volume configured systems, but the system is limited to staged fan control instead of a
fully variable sequence.
When under conventional thermostat control, the equipment responds directly to operating requests
from the thermostat device. Each thermostat input corresponds to a specific unit function, as described
in the following tables. Equipment protection functions and compressor minimum on/off timers remain
in-control, even when under conventional thermostat control.
Table 2. Cooling only, without outside air
X
Y1
NA
OPEN
NA
OPEN
NA
OPEN
NA
CLOSED
NA
OPEN
NA
CLOSED
NA
X
14
Inputs
Y2
W1/O
OPEN
OPEN
OPEN
OPEN
CLOSED
OPEN
OPEN
X
CLOSED
OPEN
OPEN
OPEN
CLOSED
OPEN
OPEN
CLOSED
OPEN
OPEN
X
X
Supply Fan
On/Off
W2
G
Request
CLOSED
ON
X
ON
X
ON
X
ON
X
ON
X
ON
X
X
OFF
Outputs
Supply Fan
Compressor
Auxiliary
Speed
Cool Stage
Heat Stage
Request
Request
Request
Min
None
Stage 1
Min
None
Full Stage
Min
None
Stage 2
Min
Stage 2
Min
Full Stage
Max
0
None
Heat Cool
Mode Status
Fan Only
None
Heat
Heat
None
Cool
None
Cool
None
Cool
None
OFF
ACC-APG002A-EN