Fault Monitoring And Reaction; Generic Fault Reaction - Danfoss PVG 16 Technical Information

Proportional valve group
Hide thumbs Also See for PVG 16:
Table of Contents

Advertisement

Technical Information
PVG 16 Proportional Valve Group

Fault Monitoring and Reaction

Generic Fault Reaction

84 |
©
Danfoss | December 2018
All proportional control PVG 16 actuators feature:
Integrated fault monitoring
Detecting spool stroke inconsistencies
Detecting internal hardware defects
Detecting demand signal inconsistencies
Fault reaction depending on the type of fault monitoring
Generic
Specific
The PVEA comes with a passive fault monitoring.
Passive fault monitoring
Passive fault monitoring does not disable the solenoid valves when an error is detected. It will continue
to operate despite that an error was detected. When the error no longer is registered the passive fault
monitoring will "forget" the error and continue as if the error was never there.
With a passive fault monitoring the following conditions will happen when an error is detected/occurs:
The LED light will switch from green to red and the error pin output will go high
The solenoid valves will continue operating at the set point given at the time of the error
Only exception is if the error is caused by the supply voltage (U
the allowed range or if the temperature measured on the internal electronics board is higher than
allowed. In these cases, the solenoid valves will be disabled.
All PVE actuators with fault monitoring are triggered by the following main events:
Control Signal Monitoring
Transducer/LVDT Supervision
Supervision of Spool Position
Float Position Monitoring
Temperature Monitoring
The Control signal voltage (U
) is continuously monitored.
S
The permissible range is between 15% and 85% of the supply voltage (U
Outside this range the PVE will switch into an error state. A disconnected U
pin (floating) is recognized as a neutral set point.
The internal LVDT wires are monitored. If the signals are interrupted or short-
circuited, the PVE will switch into an error state.
The actual position must always correspond to the demanded position (U
If the actual spool position is further out from neutral than the demanded
spool position or in opposite direction, the PVE will switch into an error state.
Spool position closer to neutral and in same direction will not cause an error
state – the situation is considered in control.
Float position must be entered or left within a time limit.
A too high delay on the 1x6 pin float PVE will cause an error state – this is
relevant for the 1x6 pin PVEH-F actuators only.
When the temperature is too high the PVE LED will light constant red and
solenoid valves will be disabled.
) being either above or below
DC
BC00000211en-000901
).
DC
S
).
S

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pvg 16 pvpPvg 16 pvsPvg 16 pvh/coversPvg 16 pvhcPvg 16 pvasPvg 16 pve ... Show all

Table of Contents