Omron E5*D Series Connection Manual page 57

General-purpose serial. rs-485 compoway/f. machine automation controller,
Hide thumbs Also See for E5*D Series:
Table of Contents

Advertisement

9.7.2.
Destination Device Error
These error codes are used for errors in the Destination Device.
●Destination Device error code [Output_CWFErrCode1, Output_CWFErrCode2]
[Output_CWFErrCode1] (End code)
Bit
15
End code
00
Normal completion
0F
FINS command error
10
Parity error
11
Framing error
12
Overrun error
13
BCC error
14
Format error
16
Sub-address error
18
Frame length error
8
7
#00 Fixed
"**" End code
Name
The command ended normally without error.
The specified FINS command could not be
executed.
The FINS response code should indicate why
the command could not be executed.
The sum total of bits whose received data is "1"
does not match the set value of the
"communications parity" bit.
Stop bit is "0".
An attempt was made to transfer new data
when the reception data buffer was already full.
The calculated BCC value is different from the
received BCC value.
- The command text contains characters other
than 0 to 9, and A to F.
- There was no SID and command text, or there
was no command text.
- "MRC/SRC" not included in command text.
- Illegal (unsupported) subaddress
- There was no subaddress, SID and command
text.
- Subaddress was less than two characters,
and there was no SID and command text
The received frame exceeds the specified
(supported) number of bytes.
0