Omron E5*D Series Connection Manual page 56

General-purpose serial. rs-485 compoway/f. machine automation controller,
Hide thumbs Also See for E5*D Series:
Table of Contents

Advertisement

●Transmission error status [Output_TransErrCode]
The data of J01_P1_TransErrSta transmission error status is stored in
Output_TransErrCode.
When a SendCmd instruction error, a destination device error or a processing number error
occurs, bits 8, 12 and 13 will change to TRUE, respectively.
[Status of each bit at a transmission error]
Bit
15
1: Transmission error
14
(Not used)
13
1: SendCmd instruction error
12
1: Destination Device error
9 to 11
(Not used)
8
1: Processing number error
7
1: FCS check error
6
(Not used)
5
1: Timeout error
4
1: Overrun error
3
1: Framing error
2
1: Parity error
0 and 1
(Not used)
16#0000 and 16#FFFF indicate the following status.
Value
16#0000
Normal end
16#FFFF
Initialized
Description
0: No transmission error
0: Normal
0: Normal
0: Normal
0: FCS check normal
0: Normal
0: Normal
0: Normal
0: Normal
Description