Allocation Of Physical Outputs - gefran GFW ADV Configuration Manual

Advanced modular power controller
Hide thumbs Also See for GFW ADV:
Table of Contents

Advertisement

ALLOCATION OF PHySICAL OUTPUTS

607
ovt. 1
608
ovt. 2
609
ovt. 3
611
ovt. 5
612
ovt. 6
613
ovt. 7
614
ovt. 8
615
ovt. 9
616
ovt. 1 0
(*) available only with GFW-E1 present
(**) available only with GFW-E2 present
Read state
82
State of output OUT1
bit
83
State of output OUT2
bit
84
State of output OUT3
bit
86
State of output OUT5
bit
87
State of output OUT6
bit
88
State of output OUT7
bit
89
State of output OUT8
bit
90
State of output OUT9
bit
91
State of output OUT10
bit
664
44
R/W
Allocation of physical output OUT 1
Allocation of physical output OUT 2 (*)
R/W
Allocation of physical output OUT 3(**)
R/W
Allocation of physical output OUT 5
R/W
R/W
Allocation of physical output OUT 6
R/W
Allocation of physical output OUT 7
R/W
Allocation of physical output OUT 8
R/W
Allocation of physical output OUT 9
Allocation of physical output OUT 10
R/W
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
OFF = Output off
R
ON = Output on
R
State of outputs (MASKOUT_OUT)
Table of output allocations
0
Output disabled
1
Output rL.1 zone 1
2
Output rL.1 zone 2
3
Output rL.1 zone 3
5
Output rL.2 zone 1
6
Output rL.2 zone 2
7
Output rL.2 zone 3
9
Output rL.3 OR rL.5 zone 1
10
Output rL.3 OR rL.5 zone 2
11
Output rL.3 OR rL.5 zone 3
13
Output rL.4 AND rL.6 zone 1
14
Output rL.4 AND rL.6 zone 2
15
Output rL.4 AND rL.6 zone 3
17
Output (rL.3 OR rL.5) zone 1...zone 3
18
Output (rL.4 AND rL.6) zone 1...zone 3
+32
to reverse output status (only for Logic/Relay)
output
NOTE: In 3-phase configuration, the state of physical output OUT1 is copied
to OUT2 and OUT3.
In case of auxiliary continuous outputs, the same output functions can not be
used on other outputs.
Ex: If out. 1 = 1 (out rL. 1 zone 1) it is not possible to set out. 5 with the same
code, if out. 5 is continuous
Table of output state
bit
0
OUT 1
1
OUT 2
2
OUT 3
4
OUT 5
5
OUT 6
6
OUT 7
7
OUT 8
8
OUT 9
9
OUT 10
80963B_MSW_GFW_11-2012_ENG
1
2
3
5
6
7
9
17
18