3.3.
Outputs
3.3.1.
J1 connector - outputs 5...8 (optional)
The J1 connector is only present if the product is equipped with the optional auxiliary outputs (O5...O8).
The available outputs can be relay type (R), digital type (D) or analogue type (W).
For technical specifications, see the Technical Data.
Use shielded cables with a cross-section of 0.25...2.5 mm2 (23-14 AWG) terminated with ferrules for connection. A shield-
ed cable is recommended for analogue outputs (W).
3.3.1.1.
Optional D-type outputs (digital)
I
+
+
+
V
Figure 16 - Digital output connection diagram
2
O5
3
O6
4
O7
5
O8
+
1
Com 5...8
81900A "MHW_GPC-40/600A"_03-2021_ENG_page 24
PIN
Name
1
Com 5-8
2
O5
3
O6
4
O7
5
O8
Option D includes 4 digital high-side current-emitting
outputs. The voltage levels range from 0 V to the product
supply value.
Description
Outputs common
Output 5 (+)
Output 6 (+)
Output 7 (+)
Output 8 (+)