Softstart For Preheating; Heating Output (Fast Cycle) - gefran GFW ADV Configuration Manual

Advanced modular power controller
Hide thumbs Also See for GFW ADV:
Table of Contents

Advertisement

SOFTSTART FOR PREHEATING

This function lets you deliver a settable power (So.P) for time (SoF), after which normal control is resumed by means
of PID control.
Activation is only at switch-on, with manual-automatic switching during Softstart (the time restarts from 0), and if the
process variable is below setpoint SP.S.
From SW version 2.02:
With softstart time SoF = 0, preheat condition PV <SP.S with settable power SO.P is continuously checked.
31
s. t v
263
SP. S
264
SO. P
147
SOF
Read state
63
STATE OF SOFTSTART
bit

HEATING OUTPUT (Fast cycle)

For outputs rL.1 (Out 1) and rL.2 (Out 2) you can set a fast cycle time (0.1 ... 20,0 sec) by setting the parameter to
64 (Heat) or 65 (Cool).
160*
rL. 1
163*
rL. 2
80963B_MSW_GFW_11-2012_ENG
Process
variable
SP
SP S
t.a.
Power
SoP
Controller in open loop
Enable selftuning,
R/W
autotuning, softstart
R/W
Softstart setpoint
R/W
Softstart power
Softstart time
R/W
OFF = Softstart in Stop
R
ON = Softstart in Start
R/W
Allocation of reference signal
R/W
Allocation of reference signal
SoF
Controller in closed loop
Autotuning
continuous
0
1
YES
2
3
YES
4
5
YES
6
Autotuning One-shot
8*
WAIT
9
10*
WAIT
11
12*
WAIT
13
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s.
+32 with automatic switching in GO if PV-SP > 1% f.s.
+64 with automatic switching in GO if PV-SP > 2% f.s.
+128 with automatic switching in GO if PV-SP > 4% f.s.
Lo.L...HI.L
-100,00....
....100,0 %
0.0 ...500,0 min
See: Generic alarms -Table of reference signals
Selftuning, autotuning, softstart table
Selftuning
NO
NO
NO
NO
YES
YES
NO
NO
NO
NO
GO
NO
YES
GO
YES
NO
GO
NO
0
Softstart
NO
NO
NO
NO
YES
YES
NO
NO
NO
NO
YES
YES
100
0,0
0,0
0
0
0
zone1
zone2
zone3
1
1
1
zone1
zone2
zone3
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfx4-ir

Table of Contents