Recommended Wire Sizes - FujiFilm FVR-Micro Instruction Manual

Advanced simple inverter
Table of Contents

Advertisement

2.3.3 Recommended wire sizes

Table 2.6 lists the recommended wire sizes. The recommended wire sizes for the main circuit
terminals for an ambient temperature of 50°C are indicated for two types of wire: HIV single wire
(for the maximum allowable temperature 75°C) .
Table 2.6 Recommended Wire Sizes
Nomi-
nal
applied
Inverter type
motor
(kW)
0.4
FVR0.4AS1S-4
FVR0.75AS1S-4
0.75
FVR1.5AS1S-4
1.5
2.2
FVR2.2AS1S-4
FVR3.7AS1S-4
3.7
0.4
FVR0.4AS1S-7
0.75
FVR0.75AS1S-7
FVR1.5AS1S-7
1.5
FVR2.2AS1S-7
2.2
*1 Use crimp terminals covered with an insulated sheath or insulating tube. Recommended wire
sizes are for HIV/IV (PVC in the EU).
Recommended wire size (mm
Main circuit power input [L1/R,
L2/S, L3/T] [L1/L, L2/N]
Grounding [
G]
w/o DCR
2.0(2.0)
2.0(3.5)
5.5(5.5)
2-5
Main circuit
Inverter
output
[U, V, W]
2.0(2.0)
2.0(2.0)
*1
2
)
Control
Braking
circuit
resistor
[P, DB]
0.5
2.0 (2.5)