Analog Output; Voltage Adjustment; Function - FujiFilm FVR-Micro Instruction Manual

Advanced simple inverter
Table of Contents

Advertisement

F30
Analog Output [FMA] (Voltage adjustment)
F31
Analog Output [FMA] (Function)
These function codes allow terminal [FMA] to output monitored data such as the output frequency
and the output current in an analog DC voltage. The magnitude of the output voltage is adjustable.
 Voltage adjustment (F30)
F30 adjusts the output voltage representing the monitored data selected by F31 within the range of
0 to 300%.
 Function (F31)
F31 specifies what is output to analog output terminal [FMA].
Data for
F31
Output frequency
0
(before slip
compensation)
Output frequency
1
(after slip
compensation)
2
Output current
3
Output voltage
PID feedback
7
amount
DC link bus
9
voltage
14
Calibration
PID command
15
(SV)
16
PID output (MV)
[FM] output
Output frequency of the inverter
(Equivalent to the motor
synchronous speed)
Output frequency of the inverter
Output current (RMS) of the
inverter
Output voltage (RMS) of the
inverter
Feedback amount under PID
control
DC link bus voltage of the
inverter
Full scale output of the meter
calibration
Command value under PID
control
Output level of the PID
controller under PID control
(Frequency command)

Function

(Monitor the following)
5-38
Meter scale
(Full scale at 100%)
Maximum frequency (F03)
Maximum frequency (F03)
Twice the inverter rated current
250 V for 200 V class series,
500 V for 400 V class series
100% of the feedback amount
500 V for 200 V class series,
1000 V for 400 V class series
This always outputs +10 VDC
(FMA function).
100% of the PID command value
Maximum frequency
(F03)

Hide quick links:

Advertisement

Table of Contents
loading