Data for
F01, C30
2
3
4
7
In addition to the frequency command sources described above, higher
priority command sources including communications link and multistep
frequency are provided.
• For frequency settings made by terminals [12] (voltage) and [C1] (current) and
by the built-in potentiometer, setting the gain and bias changes the
relationship
between those frequency settings and the drive frequency. Refer to
function code F18 for details.
For the inputs to terminals [12] (voltage) and [C1] (current), low-pass filters
can be enabled.
• Using the terminal command Hz2/Hz1 assigned to one of the digital input
terminals switches between frequency command 1 (F01) and frequency
command 2 (C30). Refer to function codes E01 to E03.
F02

Operation Method

F02 selects the source that specifies a run command for running the motor.
Data for F02
Run Command Source
0
Keypad
(Rotation direction
specified by terminal
command)
1
External signals
2
Keypad
(Forward rotation)
Enable the current input to terminal [C1] (+4 to +20 mA DC or 0 to +20 mA DC,
maximum frequency obtained at +20 mA DC).
Using function code C40 expands the input range from "+4 to +20 mA DC"
to "0 to +20 mA DC."
Enable the sum of voltage (0 to +10 VDC, maximum frequency obtained at +10
VDC) and current inputs (+4 to +20 mA DC or 0 to +20 mA DC, maximum
frequency obtained at +20 mA DC) given to terminals [12] and [C1], respectively.
Using function code C40 expands the input range from "+4 to +20 mA DC"
to "0 to +20 mA DC."
Note: If the sum exceeds the maximum frequency (F03), the maximum
frequency will apply.
Enable the built-in potentiometer (POT). (Maximum frequency obtained at full
scale of the POT)
Enable UP and DOWN commands assigned to the digital input terminals.
The UP and DOWN should be assigned to any of digital input terminals [X1] to
[X3] beforehand with any of E01 to E03 (data = 17 and 18).
Function
Description
Enable the
/
keys to run and stop the motor.
The rotation direction of the motor is specified by
terminal command FWD or REV.
Enable terminal command FWD or REV to run and
stop the motor.
Enable
/
keys to run and stop the motor.
Note that this run command enables only the
forward rotation.
There is no need to specify the rotation direction.