FujiFilm FVR-Micro Instruction Manual page 40

Advanced simple inverter
Table of Contents

Advertisement

(F codes continued)
Code
Name
F43
Current Limiter
(Mode selection)
F44
(Level)
F50
Electronic Thermal
Overload Protection for
Braking Resistor
(Discharging capability)
(Allowable average loss)
F51
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED
monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 The percentage is relative to the rated output current.
Data setting range
0:
Disable (No current limiter works.)
1:
Enable at constant speed (Disable
during ACC/DEC)
2:
Enable during ACC/constant speed
operation
20 to 180 : 3.7 kW(5HP)
(The data is interpreted as the rated
output current of the inverter for
100%.) *2
1 to 900, OFF (Cancel)
0.001 to 50.00
Incre-
ment
1
1
0.001 kW
5-5
Change
Data
Default
Unit
when
copying
setting
running
Y
Y
%
Y
Y
160
kWs
Y
OFF
Y1
Y2
Y
Y1
0.001
Y2
2