Enable Dc Braking - Dcbrk; Up And Down Commands - FujiFilm FVR-Micro Instruction Manual

Advanced simple inverter
Table of Contents

Advertisement

 Enable DC braking -- DCBRK (Function code data = 13)
This terminal command gives the inverter a DC braking command through the inverter's digital
input.(Refer to the descriptions of F20 to F22.)
 UP (Increase output frequency) and DOWN (Decrease output frequency) commands
-- UP and DOWN (Function code data = 17, 18)
• Frequency setting
When the UP/DOWN control is selected for frequency setting with a run command ON, turning the
UP or DOWN terminal command ON causes the output frequency to increase or decrease,
respectively, within the range from 0 Hz to the maximum frequency as listed below.
UP
DOWN
Data = 17
Data = 18
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Keep the current output frequency.
Increase the output frequency with the acceleration time
currently specified.
Decrease the output frequency with the deceleration time
currently specified.
Keep the current output frequency.