(E codes continued)
Code
Name
E20
Terminal [Y1] Function
E27
Terminal [30A/B/C]
Function
E30
Frequency Arrival
(Hysteresis width)
E31
Frequency Detection
(Detection level)
E32
(Hysteresis width)
E34
Overload Early Warning/
Current Detection/Low
Current Detection
E35
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED
monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
Data setting range
Selecting function code data assigns the
corresponding function to terminals [Y1] and
[30A/B/C] as listed below.
0 (1000): Inverter running
1 (1001): Frequency arrival signal
2 (1002): Frequency detected
3 (1003): Undervoltage detected
(Inverter stopped)
5 (1005): Inverter output limiting
6 (1006): Auto-restarting after momentary
power failure
7 (1007): Motor overload early warning
26 (1026): Auto-resetting
35 (1035): Inverter running 2
36 (1036): Overload prevention control
37 (1037): Current detected
38 (1038): Current detected 2
41 (1041): Low current detected
43 (1043): Under PID control
44 (1044): Motor stopped due to slow
flowrate under PID control
56 (1056): Motor overheat detected by
thermistor
57 (1057): Brake signal
59 (1059): Terminal [C1] wire break
84 (1084): Maintenance timer
87 (1087): Frequency arrival detected
90(1090): Traverse Up
91(1091): Traverse Out
99 (1099): Alarm output (for any alarm)
Setting the value in parentheses ( ) shown
above assigns a negative logic output to a
terminal.
0.0 to 10.0
0.0 to 400.0
0.0 to 400.0
0.00 (Disable), 0.01 to 100.0
Current value of 1 to 200% of the inverter
rated current
(Level)
(Timer)
0.01 to 600.0 *1
Incre-
ment
(RUN)
(FAR)
(FDT)
(LU)
(IOL)
(IPF)
(OL)
(TRY)
(RUN2)
(OLP)
(ID)
(ID2)
(IDL)
(PID-CTL)
(PID-STP)
(THM)
(BRKS)
(C1OFF)
(MNT)
(FARFDT)
(TRV_UP)
(TRV OUT)
(ALM)
0.1
0.1
0.1
0.01
0.01
5-7
Change
Data
Default
Unit
when
copying
setting
running
N
Y
N
Y
99
Hz
Y
Y
2.5
Hz
Y
Y
60.0
Hz
Y
Y
1.0
A
Y
Y1
See
Y2
Table
A.
s
Y
Y
10.00
0