Rated Voltage At Base Frequency (F05); Non-Linear V/F Patterns 1 And 2 For Frequency/Voltage - FujiFilm FVR-Micro Instruction Manual

Advanced simple inverter
Table of Contents

Advertisement

 Rated Voltage at Base Frequency (F05)
Set "0" or the rated voltage printed on the nameplate labeled on the motor.
- If "0" is set, the rated voltage at base frequency is determined by the power source of
the inverter. The output voltage will vary in line with any variance in input voltage.
- If the data is set to anything other than "0," the inverter automatically keeps the output
voltage constant in line with the setting. When any of the auto torque boost settings,
auto energy saving or slip compensation is active, the voltage settings should be equal
to the rated voltage of the motor.
 Non-linear V/f Patterns 1 and 2 for Frequency (H50 and H52)
Set the frequency component at an arbitrary point of the non-linear V/f pattern.
(Setting "0.0" to H50 or H52 disables the non-linear V/f pattern operation.)
 Non-linear V/f Patterns 1 and 2 for Voltage (H51 and H53)
Sets the voltage component at an arbitrary point of the non-linear V/f pattern.
 Maximum Output Voltage (F06)
Set the voltage for the maximum frequency 1 (F03).
If F05 (Rated Voltage at Base Frequency 1) is set to "0," settings of H50
through H53 and F06 do not take effect. (When the non-linear point is below
the base frequency, the linear V/f pattern applies; when it is above, the output
voltage is kept constant.)
• When the auto torque boost (F37) is enabled, the non-linear V/f pattern takes
no effect.
Examples:
 Normal (linear) V/f pattern
5-21

Hide quick links: