Table 2.7 Symbols, Names and Functions of the Control Circuit Terminals
Symbol
Name
[13]
Power
Power supply (+10 VDC) for an external frequency command potentiometer
supply
(Potentiometer: 1 to 5 kΩ)
for
A potentiometer of 1/2 W rating or more should be connected
potenti-
Allowable maximum output current: 10mA.
ometer
[12]
Analog
(1) The frequency is commanded according to the external analog input voltage.
setting
voltage
input
(2) Used for reference signal (PID process command) or PID feedback signal.
(3) Used as additional auxiliary setting for various main frequency commands.
[C1]
Current
(1) The frequency is commanded according to the external analog input current.
input
(2) Used for reference signal (PID process command) or PID feedback signal.
(3) Connects PTC (Positive Temperature Coefficient) thermistor for motor
(4) Used as additional auxiliary setting for various main frequency commands.
[11]
Analog
Common terminal for analog input and output signals
common
This terminal is electrically isolated from terminals [Y1E].
0 to +10 (VDC)/0 to 100 (%) (Normal operation)
+10 to 0 (VDC)/0 to 100 (%) (Inverse operation)
* Input impedance: 22 kΩ
* The allowable maximum input is +15 VDC; however, the voltage higher than
+10 VDC is treated as +10 VDC.
+4 to +20 mA DC/0 to 100% (Normal operation)
+20 to +4 mA DC/0 to 100% (Inverse operation)
+0 to +20 mA DC/0 to 100% (Normal operation)
+20 to 0 mA DC/0 to 100% (Inverse operation)
protection.
* Input impedance: 250Ω
* The allowable maximum input is +30 mA DC; however, the current larger
than +20 mA DC is treated as +20 mA DC.
Functions
2-11