Warnings And Alarms; Status Messages; Warnings/Alarm Messages - Danfoss VLT Profinet MCA 120 Operating Instructions Manual

Hide thumbs Also See for VLT Profinet MCA 120:
Table of Contents

Advertisement

Warnings and Alarms

11 Warnings and Alarms

11.1 Status Messages

11.1.1 Warnings/Alarm Messages

The LEDs on the LCP signals a warning or an alarm. A code
in the display is also shown.
A warning remains active until its cause is no longer
present. Under certain circumstances, operation of the
motor can still be continued. Warning messages are not
necessarily critical.
An alarm makes the frequency converter trip. Alarms must
be reset to restart operation once their cause has been
rectified.
Three ways of resetting alarms
By pressing [Reset]
Via a digital input with the "Reset" function
Via serial communication/optional fieldbus
NOTICE
After a manual reset pressing [Reset], the [Auto On] key
must be pressed to restart the motor.
If an alarm cannot be reset, the reason could be that its
cause has not been rectified, or the alarm is trip-locked
(see also Table 11.1).
11.1.2 Alarm List
No.
Description
1
10 V low
2
Live zero error
3
No motor
4
Mains phase loss
5
DC link voltage high
6
DC link voltage low
7
DC over-voltage
8
DC under voltage
9
Inverter overloaded
10
Motor ETR over temperature
11
Motor thermistor over temperature
12
Torque limit
13
Over Current
14
Earth Fault
15
Hardware mismatch
16
Short Circuit
17
Control word time-out
MG90U302
Operating Instructions
Alarms that are trip-locked offer additional protection,
meaning that the mains supply must be switched off
before the alarm can be reset. After being switched back
on, the frequency converter is no longer blocked and can
be reset as described, once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the
automatic reset function in 14-20 Reset Mode (Warning:
automatic wake-up is possible!)
If a warning or alarm is marked against a code in
Table 11.1, this means that either a warning occurs before
an alarm, or that it is possible to specify whether it is a
warning or an alarm that is displayed for a given fault.
This is possible, for instance, in 1-90 Motor Thermal
Protection. After an alarm or trip, the motor carries on
coasting, and the alarm and warning flash. Once the
problem has been rectified, only the alarm continues
flashing until the frequency converter is reset.
Warning
Alarm/trip
X
(X)
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
X
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
X
(X)
(X)
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
Alarm/trip lock
Parameter reference
6-01 Live Zero Timeout Function
1-80 Function at Stop
(X)
14-12 Function at Mains Imbalance
1-90 Motor Thermal Protection
1-90 Motor Thermal Protection
X
X
X
X
Parameter 8-04 Control Timeout
Function
11
11
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents