Danfoss VLT Profinet MCA 120 Operating Instructions Manual page 45

Hide thumbs Also See for VLT Profinet MCA 120:
Table of Contents

Advertisement

Parameters
8-04 Control Timeout Function
Select the time-out function. The time-out function activates
when the control word fails to be updated within the time
period specified in parameter 8-03 Control Timeout Time.
Option:
Function:
[7]
Select setup 1
Changes the set-up upon reestablishment
of communication following a control
word time-out. If communication resumes
after a time-out, parameter 8-05 End-of-
Timeout Function defines whether to
resume the set-up used before the time-
out, or to retain the set-up endorsed by
the time-out function.
[8]
Select setup 2
See [7] Select setup 1
[9]
Select setup 3
See [7] Select setup 1
[10] Select setup 4
See [7] Select setup 1
[20] N2 Override
Release
NOTICE
To change the set-up after a time-out, the following
configuration is required:
Set 0-10 Active Set-up to [9] Multi set-up and select the
relevant link in 0-12 This Set-up Linked to.
8-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control
word following a time-out. This parameter is
active only when 8-04 Control Timeout Function
is set to [7] Set-up 1, [8] Set-up 2, [9] Set-up 3 or
[10] Set-up 4.
[0] Hold set-
Retains the set-up selected in 8-04 Control
up
Timeout Function and displays a warning, until
8-06 Reset Control Timeout toggles. Then the
frequency converter resumes its original set-up.
[1] Resume
Resumes the set-up active before the time-out.
set-up
8-06 Reset Control Timeout
This parameter is active only when [0] Hold set-up has been
selected in parameter 8-05 End-of-Timeout Function.
Option:
Function:
[0] Do not reset Retains the set-up specified in
parameter 8-04 Control Timeout Function,
following a control word time-out.
[1] Do reset
Returns the frequency converter to the original
set-up following a control word time-out. The
frequency converter performs the reset and
then immediately reverts to the [0] Do not reset
setting
MG90U302
Operating Instructions
8-07 Diagnosis Trigger
Option:
[0] Disable
[1] Trigger on
alarms
[2] Trigger
alarm/warn.
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered, if the function is required. A
power-cycle is required for changes to take effect.
Option:
[0]
[1]
8-10 Control Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A will be visible in the LCP
display.
For guidelines in selection of [0] Frequency converter profile and
[1] PROFIdrive profile refer to the design guide of the related
product.
For additional guidelines in the selection of [1] PROFIdrive profile,
[5] ODVA and [7] CANopen DSP 402, see Operating Instructions for
the installed fieldbus.
Option:
[0]
[1]
[5]
[7]
8-13 Configurable Status Word STW
Option:
[0]
No function
[1]
Profile Default
*
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
Function:
Enables and controls the drive diagnosis
function.
Extended diagnosis data are not sent even if
they appear in the frequency converter.
Extended diagnosis data are sent when one or
more alarms appear.
Extended diagnosis data are sent if one or
more alarms/warnings appear.
Function:
Motor Data Std-
Select [0] for normal bus
Filt.
readouts.
Motor Data LP-
Select [1] for filtered bus
Filter
readouts of the following
parameters:
16-10 Input Power [kW]
16-11 Input Power [hp]
16-12 Motor Voltage
16-14 Motor current
16-16 Torque [Nm]
16-17 Speed [RPM]
16-22 Torque [%]
16-25 Torque [Nm] High
Function:
FC profile
PROFIdrive profile
ODVA
CANopen DSP 402
Function:
This parameter enables configuration of
bits 12–15 in the status word.
Function corresponds to the profile default
selected in 8-10 Control Profile.
8
8
43