Danfoss MCA 123 POWERLINK Operating Instructions Manual page 36

Table of Contents

Advertisement

Parameters
8-05 End-of-Timeout Function
Option:
[0] Hold set-up
[1] Resume set-
up
8-06 Reset Control Word Timeout
This parameter is active only when [0] Hold set-up has been
selected in 8-05 End-of-Timeout Function.
Option:
[0] Do not reset Retains the set-up specified in 8-04 Control
[1] Do reset
7
7
8-07 Diagnosis Trigger
This parameter enables and controls the frequency converter
diagnosis/Emergency function. In Profibus, it expands the
diagnosis data to 24 byte. In EtherCAT, it activates the
transmission of the Emergency object. In POWERLINK, it enables
the Error signaling. The Emergency/Error signaling object consists
of 8 byte of data, where byte 3 indicates an active alarm or
warning. Bit 0=1 Alarmword 1 has an active Alarm. Bit 1=1
Alarmword 2 has an active Alarm. Bit 2, reserved, Bit 3=1
Warningword 1 has an active warning. Bit 4=1 Warningword 2
has an active warning. Bits 5-7, reserved.
Option:
[0]
[1]
[2]
NOTE
The following is only valid for Profibus and EtherCAT.
-
[0] Disable: Do not send extended diagnosis/
emergency data even if they appear in the
frequency converter.
-
[1] Trigger on alarms: Send extended diagnosis/
emergency data when one or more alarms
appear in alarm 16-90 Alarm Word or 9-53 Profibus
Warning Word.
-
[2] Trigger alarms/warn.: Send extended diagnosis/
emergency data if one or more alarms or
warnings appear in alarm 16-90 Alarm Word,
34
MCA 123 POWERLINK Operating Instructions
Function:
is set to [7] Set-up 1, [8] Set-up 2, [9] Set-up 3 or
[10] Set-up 4.
Retains the set-up selected in 8-04 Control
Timeout Function and displays a warning, until
8-06 Reset Control Timeout toggles. Then the
frequency converter resumes its original set-up.
Resumes the set-up active before the time-out.
Function:
Word Timeout Function, following a control
word time-out.
Returns the frequency converter to the original
set-up following a control word time-out. The
frequency converter performs the reset and
then immediately reverts to the [0] Do not reset
setting
Function:
Disable
Trigger on alarms
Trigger alarm/warn.
MG92C102 - VLT
9-53 Profibus Warning Word, or warning
16-92 Warning Word.
Enabling diagnosis can cause increased bus traffic. Not all
fieldbus types support Diagnosis functions.
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered if the function is required. A
power-cycle is required for changes to take effect.
Option:
[0]
Motor Data Std-
Filt.
[1]
Motor Data LP-
Filter
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are visible in the LCP display. If
the parameter is changed while the frequency converter is in
operation mode, the frequency converter goes to error state, and
the control of the frequency converter is lost. This parameter
should not be changed while the motor is running, since it can
lead to a unknown state of the profile.
Option:
[0]
FC Profile
*
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
This parameter enables configuration of bits
12–15 in the status word.
[0]
No function
[1]
Profile
Function corresponds to the profile default
*
Default
selected in 8-10 Control Profile.
[2]
Alarm 68
Only set in case of an Alarm 68.
Only
[3]
Trip excl.
Set in case of a trip, except if Alarm 68
Alarm 68
executes the trip.
[10] T18 DI
The bit indicates the status of terminal 18.
status.
"0" indicates that the terminal is low
"1" indicates that the terminal is high
[11] T19 DI
The bit indicates the status of terminal 19.
status.
"0" indicates that the terminal is low
"1" indicates that the terminal is high
[12] T27 DI
The bit indicates the status of terminal 27.
status.
"0" indicates that the terminal is low
®
is a registered Danfoss trademark
Function:
Select [0] for normal bus
readouts.
Select [1] for filtered bus
readouts of the following
parameters:
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-14 Motor current
16-16 Torque [Nm]
16-17 Speed [RPM]
16-22 Torque [%]
16-25 Torque [Nm] High
Function:
Function: