Danfoss MCA 123 POWERLINK Operating Instructions Manual page 28

Table of Contents

Advertisement

Communication Profile Area
Index, sub-index
1010h 0
1010h 1
1010h 2
1010h 3
Table 6.5 1010h Store Parameters
Writing the value "save" (0x65766173) to sub-index 1,
stores all frequency converter parameters of all set-ups
into non-volatile memory, all other values are rejected.
6.2.8 1011h Restore Default Parameters
To restore factory default settings:
1.
Write the value "load" to sub-index 1.
6
6
2.
Initiate the next power cycle manually.
The default value is restored.
Index, sub-index
1011h 0
1011h 1
Table 6.6 1011h Restore Default Parameters
Writing the value "load" (0x64616F6C) restores all
frequency converter parameters of all set-ups to factory
values, except the communications parameters. All other
values are rejected, and abort code 0x08000020 is
returned. The frequency converter has to be power cycled
before the changes get active and the motor must be in
the state coast or stopped.
6.2.9 1018h Identity Object
This object contains general information about the device.
The vendor ID (sub-index 1h) contains a unique value
allocated to each manufacturer.
The manufacturer-specific product code (sub-index 2h)
identifies a specific device version.
The manufacturer-specific revision number (sub-index 3h)
consists of a major revision number and a minor revision
number.
26
MCA 123 POWERLINK Operating Instructions
Meaning
Number sub-index supported
Save option parameters
Save communication option parameters
Reserved
Meaning
Number of sub-index supported
Restore all default parameters and restart
MG92C102 - VLT
Index, sub-index Meaning
1018h 0
Number of entries
1018h 1
Vendor ID
1018h 2
Product code
1018h 3
Revision number (major revision number and
minor revision number)
1018h 4
Serial number
Table 6.7 1018h Identity Object
6.2.10 1020h CFM_VerifyConfiguration_REC
This object contains the devices local configuration date
and time. The object values are set by managing node or
configuration tool.
Index, sub-index Meaning
1020h 0
Number of entries
1020h 1
ConfDate_U32, Days since January 1, 1984
1020h 2
ConfTime_U32, milliseconds after midnight
1020h 3
ConfId_U32, assigned by the configuration tool
1020h 4
VerifyConfInvalid_BOOL, Value False indicates
that configuration was not modified since last
storage of ConfId_U32
Table 6.8 1020h CFM_VerifyConfiguration_REC
6.2.11 1030h NMT_InterfaceGroup_0h_REC
This object is used to configure and retrieve parameters of
the network interfaces (physical or virtual) via SDO.
Index, sub-index
1030h 0
1030h 1
1030h 2
1030h 3
1030h 4
1030h 5
1030h 6
1030h 7
1030h 8
1030h 9
Table 6.9 1030h NMT_InterfaceGroup_0h_REC
®
is a registered Danfoss trademark
Meaning
Number of entries
InterfaceIndex_U16
InterfaceDescription_VSTR t
InterfaceType_U8
InterfaceMtu_U16
InterfacePhysAddress_OSTR
InterfaceName_VSTR
InterfaceOperStatus_U8
InterfaceAdminState_U8
Valid_BOOL