Parameters
8-13 Configurable Status Word STW
Option:
Function:
"1" indicates that the terminal is high
[13] T29 DI
The bit indicates the status of terminal 29.
status.
"0" indicates that the terminal is low
"1" indicates that the terminal is high
[14] T32 DI
The bit indicates the status of terminal 32.
status.
"0" indicates that the terminal is low
"1" indicates that the terminal is high
[15] T33 DI
The bit indicates the status of terminal 33.
status.
"0" indicates that the terminal is low
"1" indicates that the terminal is high
[16] T37 DI
The bit indicates the status of terminal 37.
status
0" indicates T37 is low (safe stop)
"1" indicates T37 is high (normal)
[21] Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor, or
the thermistor.
[30] Brake fault
Output is Logic '1' when the brake IGBT is
(IGBT)
short-circuited. Use this function to protect
the frequency converter if there is a fault on
the brake modules. Use the output/relay to
cut out the main voltage from the frequency
converter.
[40] Out of ref.
range
[60] Comtor 0
See parameter group 13-1* ComparatorsCom-
parators. If Comtor 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61] Comtor 1
See parameter group 13-1* ComparatorsCom-
parators. If Comtor 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62] Comtor 2
See parameter group 13-1* ComparatorsCom-
parators. If Comtor 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63] Comtor 3
See parameter group 13-1* ComparatorsCom-
parators. If Comtor 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64] Comtor 4
See parameter group 13-1* ComparatorsCom-
parators. If Comtor 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65] Comtor 5
See parameter group 13-1* ComparatorsCom-
parators. If Comtor 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70] Logic Rule
See parameter group 13-4* LC-4# Logic
0
RulesLogic Rules. If Logic Rule 0 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
[71] Logic Rule
See parameter group 13-4* LC-4# Logic
1
RulesLogic Rules. If Logic Rule 1 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
[72] Logic Rule
See parameter group 13-4* LC-4# Logic
2
RulesLogic Rules. If Logic Rule 2 is evaluated as
MCA 123 POWERLINK Operating Instructions
8-13 Configurable Status Word STW
Option:
[73] Logic Rule
[74] Logic Rule
[75] Logic Rule
[80] SL Digital
[81] SL Digital
[82] SL Digital
[83] SL Digital
[84] SL Digital
[85] SL Digital
8-14 Configurable Control Word CTW
Option:
[0] None
[1] Profile default
[2] CTW Valid,
[3] Safe Option
®
MG92C102 - VLT
is a registered Danfoss trademark
Function:
TRUE, the output goes high. Otherwise, it is
low.
See parameter group 13-4*. If Logic Rule 3 is
3
evaluated as TRUE, the output goes high.
Otherwise, it is low.
See parameter group 13-4* LC-4# Logic
4
RulesLogic Rules. If Logic Rule 4 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
See parameter group 13-4* LC-4# Logic
5
RulesLogic Rules. If Logic Rule 5 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
See 13-52 SL Controller Action. The output
Output A
goes high whenever the Smart Logic Action
[38] Set digital out A high is executed. The
output goes low whenever the Smart Logic
Action [32] Set digital out A low is executed.
See 13-52 SL Controller Action. The input goes
Output B
high whenever the Smart Logic Action [39]
Set digital out B high is executed. The input
goes low whenever the Smart Logic Action
[33] Set digital out B low is executed.
See 13-52 SL Controller Action. The input goes
Output C
high whenever the Smart Logic Action [40]
Set digital out C high is executed. The input
goes low whenever the Smart Logic Action
[34] Set digital out C low is executed.
See 13-52 SL Controller Action. The input goes
Output D
high whenever the Smart Logic Action [41]
Set digital out D high is executed. The input
goes low whenever the Smart Logic Action
[35] Set digital out D low is executed.
See 13-52 SL Controller Action. The input goes
Output E
high whenever the Smart Logic Action [42]
Set digital out E high is executed. The input
goes low whenever the Smart Logic Action
[36] Set digital out E low is executed.
See 13-52 SL Controller Action. The input goes
Output F
high whenever the Smart Logic Action [43]
Set digital out F high is executed. The input
goes low whenever the Smart Logic Action
[37] Set digital out F low is executed.
Function:
Selection of control word bit 10 if it is active
low or active high.
active low
Reset
7
7