No Communication With The Frequency Converter - Danfoss MCA 123 POWERLINK Operating Instructions Manual

Table of Contents

Advertisement

Troubleshooting
9.1.2 No Communication with the
Frequency Converter
If there is no communication with the frequency converter,
proceed with the following checks:
Check 1: Is the cabling correct?
Check that the cable is mounted correctly. Check if the
corresponding XDD files L/C LED shows link activity.
Check 2: Does the hardware configuration match?
Check that the 12-60 Node ID in the master matches the
value in 12-50 Configured Station Alias
Check 3: Is the correct XDD file installed?
Download the correct XDD file from
http://www.danfoss.com/BusinessAreas/DrivesSolutions/.
Check that the process data matches the active profile in
the drive.
Check 4: What is the value of 12-69 Ethernet PowerLink
Status?
The 12-69 Ethernet PowerLink Status contains 32 bits, which
each is linked to internal information. The different bits
give an overview over possible errors.
9
9
Bit
Description Value=[
no.
0
Initialisation
State
1
Not Active
State
2
Basic
Ethernet
State
3
Pre-
Operational 1
State
4
Pre-
Operational 2
State
5
Ready to
Operate State
6
Operational
State
7
Stopped
State
8
Reserved
46
MCA 123 POWERLINK Operating Instructions
Value=[1]
Comment
0]
NMT_GS_INITIL
Mapped to
ASATION
Object 1F8Ch
(WHAT79188)
NMT_CS_NOT_
Mapped to
ACTIVE
Object 1F8Ch
(WHAT79188)
NMT_CS_BASIC
Mapped to
_ETHERNET
Object 1F8Ch
(WHAT79188)
NMT_CS_PRE_
Mapped to
OPERATIONAL_
Object 1F8Ch
1
(WHAT79188)
NMT_CS_PRE_
Mapped to
OPERATIONAL_
Object 1F8Ch
2
(WHAT79188)
NMT_CS_OPER
Mapped to
ATIONAL
Object 1F8Ch
(WHAT79188)
NMT_CS_STOP
Mapped to
PED
Object 1F8Ch
(WHAT79188)
Value shall be
read as 0
Value shall be
read as 0
MG92C102 - VLT
Bit
Description Value=[
no.
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
16
Reserved
17
Reserved
18
Reserved
19
Reserved
20
Physical link
on Port 1
21
Physical link
on Port 2
22
Reserved
23
Reserved
24
W34 source
No Op State
25
W34 source
Alarm
26
W34 source
IP Address
Conflict
27
W34 source
Invalid Node
ID
28
W34 source
Incorrect
PDO
mapping
29
Reserved
®
is a registered Danfoss trademark
Value=[1]
Comment
0]
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
Value shall be
read as 0
No link
Link present on
Mapped to
present
Port 1
object 1030h
on Port 1
subindex 7
No link
Link present on
Mapped to
present
Port 2
object 1030h
on Port 2
subindex 7
Value shall be
read as 0
Value shall be
read as 0
Mapped to
object 178Ch
(WHAT79188)
Mapped to
Alarm Word
and Alarm
Word 1
IP address
conflict
detection in
Basic Ethernet
mode
Value read from
DIP switch
Set on incorrect
Tx or Rx PDO
mapping
Value shall be
read as 0

Advertisement

Table of Contents
loading

Table of Contents