Parameters
8-14 Configurable Control Word CTW
Option:
[4] PID error
inverse
[5] PID reset I
part
[6] PID enable
8-50 Coasting Select
Option:
7
7
[0] Digital
input
[1] Bus
[2] Logic AND
[3] Logic OR
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option:
[0]
[1]
[2]
[3]
8-52 DC Brake Select
Option:
[0] Digital
input
36
MCA 123 POWERLINK Operating Instructions
Function:
When enabled, it inverts the resulting error
from the process PID controller. Available
only if "Configuration Mode" is set to "Surface
Winder", "Extended PID Speed OL" or
"Extended PID Speed CL".
When enabled, resets the I-part of the Process
PID controller. Equivalent to 7-40 Process PID
I-part Reset. Available only if "Configuration
Mode" is set to "Surface Winder", "Extended
PID Speed OL" or "Extended PID Speed CL".
When enabled, enables the extended process
PID controller. Equivalent to 7-50 Process PID
Extended PID. Available only if "Configuration
Mode" is set "Extended PID Speed OL" or
"Extended PID Speed CL".
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
Activates Start command via a digital input.
Activates Start command via the serial
communication port or fieldbus option.
Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Function:
Digital input
Bus
Logic AND
Logic OR
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTE
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1]
PM non-salient SPM.
Activates Start command via a digital input.
MG92C102 - VLT
8-52 DC Brake Select
Option:
Function:
[1] Bus
Activates Start command via the serial communi-
cation port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
Activates Start command via a digital input.
input
[1] Bus
Activates Start command via the serial
communication port or fieldbus option.
[2] Logic AND
Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3] Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option:
Function:
[0] Digital
Select control of the frequency converter
input
reverse function via the terminals (digital input)
and/or via the fieldbus.
[1] Bus
Activates the Reverse command via the serial
communication port or fieldbus option.
[2] Logic AND
Activates the Reverse command via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3] Logic OR
Activates the Reverse command via the
fieldbus/serial communication port OR via one
of the digital inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
Activates the set-up selection via a digital input.
input
[1] Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
®
is a registered Danfoss trademark