Block Errors; Modes - Emerson Rosemount 8800D Series Reference Manual

Vortex flowmeter with foundation fieldbus
Hide thumbs Also See for Rosemount 8800D Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4772, Rev FA
5.2.1

Block errors

Table 5-2
inactive for the resource block and are given here only for your reference.
Table 5-2. BLOCK_ERR Conditions
Condition
number
5.2.2

Modes

The resource block supports two modes of operation as defined by the MODE_BLK
parameter:
Resource Block
www.aotewell.com
lists conditions reported in the BLOCK_ERR parameter. Conditions in italics are
Condition name and description
0
Other
1
Block Configuration Error: A feature in FEATURES_SEL is set that is
not supported by FEATURES or an execution cycle in CYCLE_SEL is
set that is not supported by CYCLE_TYPE.
2
Link Configuration Error: A link used in one of the function blocks is
improperly configured.
3
Simulate Active: The simulation jumper is in place. Simulate active is
not an indication that the I/O blocks are using simulated data.
4
Local Override
5
Device Fault State Set
6
Device Needs Maintenance Soon
7
Input failure/process variable has bad status
8
Output Failure: The output is bad based primarily upon a bad input.
9
Memory Failure: A memory failure has occurred in FLASH, RAM, or
EEROM memory.
10
Lost Static Data: Static data that are stored in nonvolatile memory
have been lost.
11
Lost NV Data: Nonvolatile data that are stored in nonvolatile
memory
have been lost.
12
Readback Check Failed
13
Device Needs Maintenance Now
14
Power Up: The device was just powered-up.
15
Out of Service: The actual mode is out of service.
Automatic (Auto) The block is processing its normal background memory checks.
Out of Service (OOS) The block is not processing its tasks. When the resource
block is in OOS, all blocks within the resource (device) are forced into OOS. The
BLOCK_ERR parameter shows OUT OF SERVICE. In this mode, you can make
changes to all configurable parameters. The target mode of a block may be
restricted to one or more of the supported modes.
sales@aotewell.com
Industry Automation
Resource Block
March 2016
71
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 8800drRosemount 8800dRosemount 8800ddRosemount 8800dw

Table of Contents