Emerson Rosemount 8800D Series Reference Manual page 87

Vortex flowmeter with foundation fieldbus
Hide thumbs Also See for Rosemount 8800D Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4772, Rev FA
Table 6-2. Analog Input Function Block System Parameters
Index
Available
Parameter
No.
values
LO_LIM
30
Out_Scale
LO_LO_ALM
36
Not applicable None
LO_LO_LIM
32
Out_Scale
LO_LO_PRI
31
0 – 15
LO_PRI
29
0 – 15
LOW_CUT
17
> = 0
MODE_BLK
05
Auto Manual
Out of Service
OUT
08
Out_Scale
10%
OUT_D
37
Discrete_State
1 – 16
OUT_SCALE
11
Any output
range
PV
07
Not applicable Out_Scale
PV_FTIME
18
> = 0
SIMULATE
09
Not applicable None
ST_REV
01
Not applicable None
Analog Input Function Block
www.aotewell.com
Units
Default
(2)
- infinity
(2)
Out_Scale
Uninitialized
(2)
(2)
Out_Scale
- infinity
None
0
None
0
0
(2)
Out_Scale
None
Not
applicable
(2)
±
Not
(2)
Out_Scale
applicable
None
Disabled
All available
none
(2)
Not
applicable
Seconds
0
Disable
0
sales@aotewell.com
Analog Input Function Block
Read/Write
Description
Read and Write The setting for the alarm limit
used to detect the LO alarm
condition.
Read only
The LO LO alarm data, which
includes a value of the alarm, a
timestamp of occurrence and
the state of the alarm.
Read and Write The setting for the alarm limit
used to detect the LO LO alarm
condition.
Read and Write The priority of the LO LO alarm.
Read and Write The priority of the LO alarm.
Read and Write If percentage value of
transducer input fails below
this, PV = 0.
Read and Write The actual, target, permitted,
and normal modes of the
block. Target: The mode to "go
to" Actual: The mode the
"block is currently in"
Permitted: Allowed modes that
target may take on Normal:
Most common mode for target
Read and Write The block output value and
status.
Read and Write
Discrete output to indicate a
selected alarm condition.
Read and Write The high and low scale values,
engineering units code, and
number of digits to the right of
the decimal point associated
with OUT.
Read only
The process variable used in
block execution.
Read and Write The time constant of the
first-order PV filter. It is the
time required for a 63% change
in the IN value.
Read and Write A group of data that contains
the current transducer value
and status, the simulated
transducer value and status,
and the enable/disable bit.
Read only
The revision level of the static
data associated with the
function block. The revision
value will be incremented each
time a static parameter value
in the block is changed.
Industry Automation
March 2016
77
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 8800drRosemount 8800dRosemount 8800ddRosemount 8800dw

Table of Contents