Transducer Block
March 2016
Table 4-1. Transducer Block Parameters
Parameter
WETTED_MATERIAL
XD_ERROR
XMTR_MODE
4.2.1

Block/transducer errors

The BLOCK_ERR conditions are listed in
Table
are provided for reference only.
Table 4-2. BLOCK_ERR Conditions
Condition
number
52
www.aotewell.com
Index
number
Definition
37
Construction materials of those items in contact with the process:
2 = 316 SST
3 = Alloy
Each material has a different coefficient of expansion.
Wetted material is used as an input to the compensated K-factor
calculation.
11
XD_ERROR is a transducer block alarm subcode.
73
For a transmitter equipped with a thermocouple to measure the process
temperature this parameter is used to enable or disable the
thermocouple. This allows the use of one electronics board stack spare
to replace MTA and non-MTA models.
1 = Thermocouple disabled, 2 = Thermocouple enabled
4-3. The conditions that are shown in italics are inactive for the transducer block and
Condition name and description
0
Other
1
Block Configuration Error
2
Link Configuration Error
3
Simulate Active
4
Local Override
5
Device Fault State Set
6
Device Needs Maintenance Soon
7
Input Failure/Process Variable Has Bad Status
8
Output Failure
9
Memory Failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Now
14
Power Up: The device was just powered-up.
sales@aotewell.com
Table
4-2. The XD_ERROR conditions are listed in
Industry Automation
Reference Manual
00809-0100-4772, Rev FA
Transducer Block