3.6.6

Hardware configuration

The hardware jumpers on the flowmeter enable you to set the fieldbus simulate enable and
transmitter security (see
housing cover from the end of the flowmeter. If the flowmeter does not include an LCD
display, the jumpers are accessible by removing the cover on the electronics side. If the
flowmeter includes an LCD display option, the fieldbus simulate enable and security
jumpers are found on the face of the LCD display (see
Note
If you will be changing configuration variables frequently, leave the security lockout jumper
in the OFF position to avoid exposing the flowmeter electronics to the plant environment.
Set jumpers during the commissioning stage to avoid exposing the electronics to the plant
environment.
Figure 3-19. Fieldbus Simulate Enable and Transmitter Security Jumpers
3.6.7

Simulate enable

The simulate enable jumper is used in conjunction with the Analog Input (AI) function block
simulation. The jumper is also used as a lock-out feature for the AI function block. To enable the
simulate enable feature, the jumper must transition from OFF to ON after power is applied to the
transmitter, preventing the transmitter from being accidentally left in simulator mode.
Installation
www.aotewell.com
Figure
3-19). To access the jumpers, remove the electronics
sales@aotewell.com
Industry Automation
Installation
Figure
3-20).
+86-755-8660-6182
March 2016
41