Analog Input Function Block
March 2016
Table 6-2. Analog Input Function Block System Parameters
Index
Available
Parameter
No.
values
CHANNEL
15
1 = Flow
2 = Signal
strength
3 = Electronics
temp.
4 = Process
temp.
5 = Process
density
FIELD_VAL
19
0 – 100
GRANT_DENY 12
Program Tune
Alarm Local
HI_ALM
34
Not applicable None
HI_HI_ALM
33
Not applicable None
HI_HI_LIM
26
Out_Scale
HI_HI_PRI
25
0 – 15
HI_LIM
28
Out_Scale
HI_PRI
27
0 – 15
IO_OPTS
13
Low Cutoff
Enable/Disable
L_TYPE
16
Direct Indirect
Indirect Square
Root
LO_ALM
35
Not applicable None
76
www.aotewell.com
Units
Default
None
AI1=1 (Flow)
AI2=2 (Signal
Strength)
AI3, AI4,
(1)
AI5=0
(Uninitialized)
(1)
(1)
Percent
Not
applicable
None
Not
applicable
Uninitialized
Uninitialized
(2)
(2)
Out_Scale
+ infinity
None
0
(2)
(2)
Out_Scale
+ infinity
None
0
None
Disable
None
Direct
Uninitialized
sales@aotewell.com
Reference Manual
00809-0100-4772, Rev FA
Read/Write
Description
Read and Write The CHANNEL value is used to
select the measurement value.
Refer to the appropriate device
manual for information about
the specific channels available
in each device. You must
configure the CHANNEL
parameter before you can
configure the XD_SCALE
parameter.
Read only
The value and status from the
transducer block or from the
simulated input when
simulation is enabled.
Read and Write Normally the operator has
permission to write to
parameter values, but Program
or Local remove that
permission and give it to the
host controller or a local
control panel.
Read only
The HI alarm data, which
includes a value of the alarm, a
timestamp of occurrence and
the state of the alarm.
Read only
The HI HI alarm data, which
includes a value of the alarm, a
timestamp of occurrence and
the state of the alarm.
Read and Write The setting for the alarm limit
used to detect the HI HI alarm
condition.
Read and Write
The priority of the HI HI alarm.
Read and Write The setting for the alarm limit
used to detect the HI alarm
condition.
Read and Write The priority of the HI alarm.
Read and Write Allows the selection of
input/output options used to
alter the PV. Low cutoff
enabled is the only selectable
option.
Read and Write Linearization type. Determines
whether the field value is used
directly (Direct), is converted
linearly (Indirect), or is
converted with the square root
(Indirect Square Root).
Read only
The LO alarm data, which
includes a value of the alarm, a
timestamp of occurrence and
the state of the alarm.
Analog Input Function Block