Connection Wiring

Terminal Block Wiring
These connection diagrams apply to the part numbers listed below.
FST020
Figure 5-4
Note
4 to 20 mA current output Channel 2
It is not required to use shielded cables for the pure 4 to 20 mA current output.
Table 5-1
Input/Output Wiring
Pin#
Signal
1
Io1+
2
Io1-
3
Chassis
4
C
5
NO
6
NC
7
Chassis
8
PULSE OUTPUT +
9
PULSE OUTPUT -
10
Chassis
11
NO TOT +
12
NO TOT -
13
CLR TOT +
14
CLR TOT -
15
Modbus_B
16
Modbus _A
17
Chassis
FST020 IP65 NEMA 4X
Operating Instructions, 09/2017, A5E41425845-AB
5.4 Transmitter power supply, communications and I/O connections
Terminal board channels and pin numbers
Function
Isolated Loop Supply
Isolated Loop Return
Ground
Common
Normally Open
Normally Closed
Ground
Isolated Transistor
Isolated Transistor
Ground
DIGITAL INPUT +
DIGITAL INPUT -
DIGITAL INPUT +
DIGITAL INPUT -
Differential +
Differential -
Ground
SITRANS FST020
7ME3570..._...
Spannable 4-20mA output (Loop Powered) This
output also provides a fault indication by drop‐
ping to 2mA if assigned to flow rate and under
fault conditions.
Ground
Relay Output
Relay Output
Relay Output
Ground
Menu selection: PGEN, POS TOTAL, NEG TO‐
TAL
Ground
Stops Totalizer from incrementing.
Clears Totalizer
Serial communication, Modbus protocol
Serial communication, Modbus protocol
Ground
Connecting
Description
31