Siemens SITRANS F Operating Instructions Manual page 117

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
10018
Float / 4
8807
Float / 4
8814
Unsigned / 2
8815
Float / 4
7146
Float / 4
8886
Float / 4
8888
Float / 4
FST020 IP65 NEMA 4X
Operating Instructions, 09/2017, A5E41425845-AB
Parameter
Description
Lower range
Lower process viscosi‐
value viscosity
ty value that is mapped
to the lower nominal
range boundary selec‐
ted by Current mode
(8806). Applicable if
Process value (8802) =
21 or 29.
Damping value
Time constant of damp‐
ing filter for current out‐
put signal.
Fail-safe behav‐
Current output reaction
ior
in case of a fault.
Fail-safe value
Output value in case of
a fault and when Fail-
safe behavior (8814) is
configured to 4.
Forced value
Forced value when
forcing is active.
Offset adjust‐
Command to trim the
ment
lower range value of
the loop current.
Simulate a loop current
of 4.0 mA, measure the
current with an ampere
meter and write the
measured value to this
register.
Gain adjustment Command to trim the
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an am‐
pere meter and write
the measured value to
this register.
A.9 Modbus holding register tables
Default value
Value range /
[units]
Setting options
(units register)
0.0
-
[m²/s]
(7524)
0.0
0.0 - 100.0
[s]
0
● 0: Lower fault current
● 1: Upper fault current
● 2: Last valid value
● 3: Disabled
● 4: Custom value
0.0
0.0 - 25.0
[mA]
4.0
3.5 - 25.0
[mA]
[mA]
0.0 - 25.0
[mA]
0.0 - 25.0
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Write on‐
ly
Write on‐
ly
117