Siemens SITRANS F Operating Instructions Manual page 115

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
8868
Float / 4
8810
Float / 4
8812
Float / 4
8870
Float / 4
8872
Float / 4
10000
Float / 4
FST020 IP65 NEMA 4X
Operating Instructions, 09/2017, A5E41425845-AB
Parameter
Description
Lower range
Lower volume flow val‐
value volume
ue that is mapped to
flow
the lower nominal
range boundary selec‐
ted by Current mode
(8806). Applicable if
Process value (8802) =
1.
Upper range
Upper mass flow value
value mass flow
that is mapped to the
upper nominal range
boundary selected by
Current mode (8806).
Applicable if Process
value (8802) = 0.
Lower range
Lower mass flow value
value mass flow
that is mapped to the
lower nominal range
boundary selected by
Current mode (8806).
Applicable if Process
value (8802) = 0.
Upper range
Upper process density
value density
value that is mapped to
the upper nominal
range boundary selec‐
ted by Current mode
(8806). Applicable if
Process value (8802) =
2.
Lower range
Lower process density
value density
value that is mapped to
the lower nominal
range boundary selec‐
ted by Current mode
(8806). Applicable if
Process value (8802) =
2.
Upper range
Upper velocity value
value velocity
that is mapped to the
upper nominal range
boundary selected by
Current mode (8806).
Applicable if Process
value (8802) = 18, 19 or
31.
A.9 Modbus holding register tables
Default value
Value range /
[units]
Setting options
(units register)
0
-
[m
/s]
3
(7500)
0.2 • max.
-
mass flow
[kg/s]
(7400)
0.0
-
[kg/s]
(7400)
Max. density
-
[kg/m
]
3
(7600)
0.08
-
[kg/m
]
3
(7600)
1.0
-
[m/s]
(8014 / 7648)
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
115