Siemens SITRANS F Operating Instructions Manual page 124

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Modbus communication
A.9 Modbus holding register tables
Modbus
Data type /
register
Size in bytes
10240
Float / 4
10242
Float / 4
9408
Float / 4
9592
Unsigned / 2
9481
Unsigned / 2
9439
Unsigned / 2
9440
Float / 4
7163
Float / 4
124
Parameter
Description
Upper range
Upper process viscosi‐
value viscosity
ty value that is mapped
to the upper nominal
range boundary selec‐
ted by Frequency value
high (9435). Applicable
if Process value (9404)
= 21 or 29.
Lower range
Lower process viscosi‐
value viscosity
ty value that is mapped
to the lower nominal
range boundary selec‐
ted by Frequency value
low (9437). Applicable
if Process value (9404)
= 21 or 29.
Damping filter
Time constant of damp‐
ing filter for frequency
output signal.
Fail-safe activa‐
Fail-safe activation con‐
tion condition
dition.
Fail-safe min.
Minimum time the out‐
time
put stays in fail-safe be‐
havior.
Fail-safe behav‐
Frequency output reac‐
ior
tion in case of a fault.
Fail-safe value
Output value in case of
a fault and when Fail-
safe behavior (9439) is
configured to 4.
Forced value
Forced value when
forcing is active.
Default value
Value range /
[units]
Setting options
(units register)
1.0
-
[m²/s]
(7524)
0.0
-
[m²/s]
(7524)
0.0
0.0 - 100.0
[s]
1
● 0: Bad status of
selected process
value
● 1: Active
Maintenance alarm
or Failure (NAMUR)
0
0 - 100
[s]
2
● 0: Frequency value
low
● 1: Frequency value
high
● 2: Last valid value
● 3: Disabled
● 4: Custom value
0.0
0.0 - 12500.0
[Hz]
1.0
0.0 - 12500.0
[Hz]
Operating Instructions, 09/2017, A5E41425845-AB
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write