Figure 9-56: Emergency Menu - Ametek i Series User Manual

Table of Contents

Advertisement

User Manual
410Hz for 5 sec.
407Hz for 4 sec.
LOW FREQUENCY
This test will change the output frequency in the following sequence:
375Hz for 1 sec.
380Hz for 4 sec.
390Hz for 5 sec.
393Hz for 4 sec.
9.8.1.7.3 EMERGENCY TEST
From the MIL704 main menu (Figure 9-53) scroll to the EMERGENCY AC entry using the up and
down cursor keys. Press the ENTER key to select the EMERGENCY screens. The screen will
appear as shown in Figure 9-56.
The EMERGENCY SCREEN has the following tests:
1
VOLTAGE
2
FREQUENCY
The above tests can be selected by scrolling to the highlighted selection using the up and down
key and the ENTER key to start the selected test.
VOLTAGE
This test will change the output voltage in the following sequence:
108V for 1 minute.
118V for 1 minute.
115V for 1 minute.
The
key (backspace) will terminate the test at any time.
FREQUENCY
This test will change the output frequency in the following sequence:
393Hz for 1 minute.
407Hz for 1 minute.
400Hz for 1 minute.
The
key (backspace) will terminate the test at any time.
i Series / iX Series

Figure 9-56: Emergency Menu

245