LED
RUN
ERR
COMM
BF
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
: On /
: Flashing / ×: Off
Setting Node Address
Set drive parameter F6-30 to a node address (Range 0 to 125) unique to the network.
YASKAWA ELECTRIC SIEP C730600 42A YASKAWA AC Drive-Option Card PROFIBUS-DP Technical Manual
Table 4 Understanding LED Display
Communication Status
The drive has no power.
SI-P3 is not properly connected to the
No power.
drive, and therefore is not receiving enough
power.
• Checking connection with the
• SI-P3 is reading the node address or
drive
parameter configuration
• Waiting for data from the
• Waiting for initial input data from master
master.
device.
SI-P3 Self-diagnostics error
The PROFIBUS-DP Option is damaged.
• Problem initializing the drive and SI-P3
Problem connecting to the drive.
• Incorrect node address.
Waiting for data from the master device
Waiting for data from the master
(Set_Parm_Message or
device.
Chk_Cfg_Message).
Data is incorrect or PROFIBUS-
The communication procedure in the
DP Option timed out waiting for
master is set incorrectly.
data.
Sending or receiving data.
4 PROFIBUS-DP Option Components
Possible Cause
• Check all wiring to the drive, then turn the power on.
• Shut the drive off and see if the PROFIBUS-DP Option is
connected properly. Turn the power back on again.
• Cycle power to the drive. If the LED status does not change,
replace the PROFIBUS-DP Option.
• Cycle power to the drive. If the LED status does not change,
replace the PROFIBUS-DP Option
• Check the node address setting in the drive (parameter F6-10).
• Check the network settings in the master
• Make sure the master device is operating normally
• Check the terminal resistance settings on the data line
• Look for any problems with the data line, or if the connector
• See if the data line connected properly to the drive's main
circuit.
• Check the communication procedure settings in the master.
Solution
9