YASKAWA SI-P3 Technical Manual page 30

Ac drive-option card profibus-dp
Hide thumbs Also See for SI-P3:
Table of Contents

Advertisement

8 Parameter Process Data Object Formats
DPV0 PNU
Description
Number
0
002CH MEMOBUS/Modbus #
0
002DH MEMOBUS/Modbus #
0
002EH MEMOBUS/Modbus #
0
002FH MEMOBUS/Modbus #
0
0030H MEMOBUS/Modbus #
0
0031H MEMOBUS/Modbus #
0
0032H MEMOBUS/Modbus #
0
0033H MEMOBUS/Modbus #
0
0034H MEMOBUS/Modbus #
0
0
00FFH MEMOBUS/Modbus #
Note: When PNU is set to 0 and INDEX is set to MEMOBUS/Modbus register number, V1000 parameter values can be read and written instead of using PNU number.
Note: MEMOBUS/Modbus register C1-01 is 200Hex
When PNU is 0 and INDEX is 200H(512 dec), C1-01 setting value can be read and written instead of using PNU 31(dec) and INDEX 01.
Example: Writing to C1-01
Command setting
Data type
PKE
IND
PWE
STW
HSW
Response
Data type
PKE
IND
PWE
STW
HSW
Example: Reading to d1-17
Command setting
Data type
PKE
IND
PWE
STW
HSW
Response
Data type
PKE
IND
PWE
STW
HSW
Example: Writing to RAM with the Enter command
Command setting
Data type
PKE
IND
PWE
STW
HSW
30
INDEX
44
45
46
47
48
49
50
51
52
255
Settings
701FH
7: Change parameter value in array (word)
1FH = 31 (C1 parameter)
1
C1-01
10
Assign 10
up to Master command
up to Master command
Settings
401FH
4: Transfer parameter value (array word)
1FH = 31 (C1 parameter)
1
C1-01
0
N/A
up to drive status
up to drive status
Settings
6029H
6: Request parameter value from array
29H = 41 (d1 parameter)
11H
11H = 17 (d1-17)
0
N/A
up to Master command
up to Master command
Settings
4029H
4: Transfer parameter value (array word)
29H = 41 (d1 parameter)
11H
d1-17
258H
d1-17 value
up to drive status
up to drive status
Settings
212CH
2: Change parameter value (word)
12CH = 300
0
N/A
0
N/A
up to Master command
up to Master command
YASKAWA ELECTRIC SIEP C730600 42A YASKAWA AC Drive-Option Card PROFIBUS-DP Technical Manual
Description
Description
Description
Description
Description

Advertisement

Table of Contents
loading

Table of Contents