Handshaking Register
Handshaking is used to synchronize the timing of the sending or receiving of MEMOBUS/Modbus message data between the SI-P3 card and the
PROFIBUS-DP master.
When the master toggles bit 7 of the handshaking register in the output data, the SI-P3 starts to process the data in the MEMOBUS/Modbus
registers. Ensure that the data in the MEMOBUS/Modbus registers is valid before toggling bit 7.
When the SI-P3 toggles bit 7 of the handshaking register in the input data to the same value as handshake register bit 7 in the output data, the content
of the input data MEMOBUS/Modbus registers is valid.
Handshaking Output Register
PROFIBUS-DP Master to SI-P3 Card
Bit 7
6
5
4
HS
Bit
Name
7
HS
1 to 6
0
INIT
Handshaking Input Register
SI-P3 Card to PROFIBUS-DP Master
Bit 7
6
5
4
HS
STATUS
Bit
Name
7
HS
5 to 6
STATUS
<1>
1 to 4
WD
<1>
0
<1> STATUS and WD are for reference.
YASKAWA ELECTRIC SIEP C730600 42A YASKAWA AC Drive-Option Card PROFIBUS-DP Technical Manual
3
2
1
0
INIT
Handshaking bit. Synchronizes send and receive timing. Changes status when sending new command messages.
Note: This bit is reset to 0 at power up or by setting the handshaking output register bit INIT to 1.
Not used
Clears the handshaking bit to 0
3
2
1
0
WD
Handshaking bit. Synchronizes send and receive timing. Changes status when sending new command messages.
Note: This bit is reset to 0 at power up or by initializing the handshaking output register bit INIT back to 0.
Status of the data exchange between the PROFIBUS-DP master and the drive.
00H: Idle
01H: SI-P3 sends a MEMOBUS/Modbus command to the drives.
10H: SI-P3 waits for a MEMOBUS/Modbus response from the drives.
11H: SI-P3 receives a MEMOBUS/Modbus response from the drives.
Counter increases every 64 ms
Not used
7 Conventional Formats
Function
Function
19