Parameter
Max_Initiate_PDU_Length
Modular_Station
Max_Module
Max_Input_Len
Max_Output_Len
Max_Data_Len
Max_User_Prm_Data_Len
Ext_User_Prm_Data_Const(0)
Ext_User_Prm_Data_Ref(0)
Ext_User_Prm_Data_Ref(0)
Max_Diag_Data_Len
Unit_Diag_Bit(0024)
Unit_Diag_Bit(0025)
Unit_Diag_Bit(0026)
Unit_Diag_Bit(0027)
Module = "Basic data" 0x72
1
EndModule
Module = "Extended Data 1" 0x5F, 0x6F
2
EndModule
Module = "Extended Data 2" 0x55, 0x65
3
EndModule
Module = "PPO Type 1" 0xF3, 0xF1
4
EndModule
Module = "PPO Type 2" 0xF3, 0xF5
5
EndModule
Module = "PPO Type 3" 0xF1
6
EndModule
Module = "PPO Type 4" 0xF5
7
EndModule
Module = "PPO Type 5" 0xF3, 0xF9
8
EndModule
Module = "PPO Type 1 (No Cons.)" 0x73, 0x71
9
EndModule
Module = "PPO Type 2 (No Cons.)" 0x73, 0x75
10
EndModule
Module = "PPO Type 3 (No Cons.)" 0x71
11
EndModule
Module = "PPO Type 4 (No Cons.)" 0x75
12
EndModule
Module = "PPO Type 5 (No Cons.)" 0x73, 0x79
13
EndModule
Supported PNU
Supported PNU No.
900
901
902
903
904
905
YASKAWA ELECTRIC SIEP C730600 42A YASKAWA AC Drive-Option Card PROFIBUS-DP Technical Manual
Setting Value
52
1
1
32
32
64
4
0x40,0x01,0x00,0x01
1
2
11
"Undervoltage Condition"
"Inverter Communications Error"
"PNU915: Illegal PNU configured"
"PNU916: Illegal PNU configured"
Data type
Write
Octet String 12
Octet String 20
Octet String 4
Octet String 12
Unsigned 16
Octet String 28
8 Parameter Process Data Object Formats
Note
Modular station.
Maximum # of modules: 1
Maximum # of input bytes
Maximum # of output bytes
Maximum # of data bytes
Maximum diagnostic length
Read
Type 1 PPO-Write
Type 2 PPO-Write
Type 3 PPO-Write (DP-V1only)
Type 4 PPO-Write (DP-V1only)
Current PPO-Write
Type 5 PPO-Write
Description