Connect To Knx; Connect To Modbus; Connect To Modbus Rtu; Connect To Modbus Tcp - IntesisBox IBOX-MBS-KNX-100 User Manual

Modbus server knx tp-1 (eib)
Table of Contents

Advertisement

Modbus Server – KNX
®
IntesisBox

4.2 Connect to KNX

Connect + and – terminals of the KNX bus to the IntesisBox KNX connector (Figure 4.1).
The polarity is important. Once connected correctly the KNX Tx led (Figure 4.1) will start
blinking. If that doesn't happen check that the cable is connected properly.
How to check if there is communication with the KNX bus is explained in the LinkBoxMB
Manual (section 5).

4.3 Connect to Modbus

4.3.1 Connect to Modbus RTU

Connect the communication cable coming from the Modbus RTU network to the port marked
as Modbus RTU of IntesisBox (Figure 4.1). Two methods to connect to the Modbus network
can be used:
The RS485 port if the network is RS485 2-wire. Connect the + and the – to the
respective port in the master device (polarity matters)
The RS232 port if the connection is point to point to one single master.
IntesisBox
DB9 F
RX
2
TX
3
GND
5
How to check if there is communication with the Modbus bus is explained in the LinkBoxMB
Manual (section 5).

4.3.2 Connect to Modbus TCP

Connect the communication cable coming from the network hub or switch to the ETH port
(Figure 4.1) of IntesisBox. The cable to be used depends on where the IntesisBox is being
connected:
Connecting directly to a Modbus TCP master device:
CAT5 cable
Connecting to a hub or switch of the LAN of the building: a straight Ethernet UTP/FTP
CAT5 cable
In case there is no communication with the IntesisBox, check that the Modbus TCP devices
they are operative and reachable from the network connection used by IntesisBox. Check
the IntesisBox Ethernet interface sending Pings to its IP address using a PC connected to
the same Ethernet network.
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
Modbus RTU Connection
EIA232 (Crossed)
Table 4.1 Modbus RS232 cable pinout
User's Manual r18 eng
Master RTU
DB9 F
2
RX
3
TX
5
GND
crossover Ethernet UTP/FTP
URL
http://www.intesisbox.com
Email
info@intesisbox.com
tel
+34 938047134
14 /
31

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IBOX-MBS-KNX-100 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Ibox-mbs-knx-aIbox-mbs-knx-b

Table of Contents