Increased controller factors in the current control loop:

The dead time in the current control loop is the decisive factor for the
attainable controller factors, and therefore for the attainable bandwidth. With
MP2450, you can activate compensation of this dead time. After activation,
you have to repeat the current controller adjustment. Usually you can then set
considerably higher current controller factors. The higher the controller
factors, the larger the bandwidth of the current controller. The bandwidth of
the current control loop can be evaluated with the Bode diagram function of
the TNCopt commissioning and diagnostic software (see TNCopt User's
Manual).
However, the noise in the current—and as a result, the loudness of the drive—
increase when the current controller bandwidth is increased.
D feedforward for optimization of the current controller command
action:
With MP2440, you activate feedforward with proportionally differentiating
behavior for the torque-generating current. This way you achieve an optimized
command action of the current controller.
The parameter MP2440 indicates the cutoff frequency in Hertz [Hz] up to
which feedforward is active. When this cutoff frequency is reached,
feedforward is deactivated by a low-pass element. It is therefore also referred
to as PDT
feedforward in the following.
1
The following table shows the maximum possible cutoff frequency depending
on the PWM frequency of the drive. The higher the cutoff frequency, the larger
the bandwidth of the current controller regarding its command action. At the
same time, however, the noise in the current—and as a result, the loudness
of the drive— increase. If you enter 0 Hz, feedforward is deactivated.
Maximum values for parameter MP2440 as a function of the PWM frequency:
PWM frequency
3333 Hz
4000 Hz
5000 Hz
6666 Hz
8000 Hz
10000 Hz
Adjustment of the current controller if increased current controller
factors are active over MP2450:
Note
For standard drives, it is usually not necessary to increase the current
controller bandwidth. In general, the increase is only useful if the drives are
connected directly without an interconnected gear.
Maximum value for MP2440
800 Hz
960 Hz
1200 Hz
1600 Hz
1920 Hz
2400 Hz
HEIDENHAIN Technical Manual iTNC 530 HSCI