7.10 DIMODE related scenarios

DIMODE Parameter Changes

The following are examples of the DIMODE parameter when modified in different
views.
IOM
View
DI24V,
Project
DISOE
DI24V
Monitoring
DI24V
Monitoring
DISOE
Monitoring
DISOE
Project
DISOE
Project
R500
April 2017
DIMODE
Old value:
LowLatency
New value:
Normal
Old value:
LowLatency
New value:
Normal
Old value:
Normal
New value:
LowLatency
Old value:
LowLatency/Normal/
Sequence of Events
New value:
LowLatency/Normal/
Sequence of Events
Old value:
Sequence of Events
some channels have
EVTOPT = Sequence
of Events
New value:
LowLatency
Old value:
Series 8 I/O User's Guide
Honeywell
7. Series 8 I/O Operations
7.10. DIMODE related scenarios
Description
Configuration changes successfully
Throws an error "Invalid access
level "
Throws an error "Invalid access
level "
Throws an error "Invalid access
level "
Throws an error "DIMODE
incompatible with EVTOPT on one
or more channels"
Reload the CMs with channel block
after changing EVTOPT to NONE
on the channels with option
Sequence of Events.
Reload the IOM.
Configuration is loaded successfully
Configuration changes
successfully.
223