Using Block Copy; Defining Analog Input Channel Blocks; Overview; Table 49 Hart Parameters - Honeywell Series 8 I/O User Manual

Table of Contents

Advertisement

6. Series 8 I/O Configuration

6.7. Defining Analog Input Channel Blocks

Parameters exposed after HART is enabled
The following table displays parameters that are only exposed when HART is enabled -
all located on the Configuration tab.
Parameter
ACCEPTRNG
URL,
URV
LRV
LRL
HPVMISM
NOTE: Only 1-5V sensor type is supported when HART is enabled.

Using Block Copy

Parameter values not copied during Block Copy
CHANNUM are the only configuration parameter values not copied during a Block Copy
operation.
6.7
Defining Analog Input Channel Blocks

Overview

The Analog Input channel block represents a single analog input point on either an
ANALOG INPUT WITH HART or TC/RTD I/O Module. The type of analog input IOM
required is based on the:
type of field sensor that is providing the input to the channel
PV characterization options you select (as listed in the table in Determining PV
Characterization):
Channels contained within ANALOG INPUT and ANALOG INPUT WITH HART IOM
is generally used for control points. Channels located in the TC/RTD IOM are generally
used for data acquisition points.
The analog input channel converts an analog PV signal received from a field sensor to
engineering units for use by other function blocks in the C300, and by the rest of
Experion.
To accomplish this function, the analog input channel, as illustrated in the figure below,
performs:
Analog-to digital conversion
182

Table 49 HART parameters

Available
Yes
Yes
Yes
Yes
Yes
Yes
Series 8 I/O User's Guide
Honeywell
R500
April 2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents