Analog Input Wiring; Table 11 Analog Input 6 Inch, Hart/Non-Hart Analog Input, Non-Redundant Terminal - Honeywell Series 8 I/O User Manual

Table of Contents

Advertisement

4. Series 8 IOTA Pinouts
4.1. HART/Non-HART Analog Input IOTA (Models 8X-TAIXA1, 8X-TAIXB1)
Table 11 Analog Input 6 inch, HART/non-HART Analog Input, non-
Channels
For channels
Channels 1 through 16
1 through 16

Analog Input wiring

Field wiring and module protection
Individual field wiring is protected by an internal protection circuit permitting the
following:
Each signal can be shorted in the field with no damage to the module or board. Other
channels on the same IOM are not affected.
Two-wire transmitter wiring
The Analog Input IOM/IOTA is optimized for use with classic two-wire transmitters. All
16 channels can accept inputs from two-wire transmitters without any special wiring or
jumper options.
54
redundant terminal block 2
Signal screw
Channels 1 through 16
TB1
pin 1, 3, 5, 7, 9, 11, 13,
15, 17, 19, 21, 23,
25, 27, 29, 31
TB1
pin 2, 4, 6, 8, 10, 12, 14,
16, 18, 20, 22, 24,
26, 28, 30, 32
250ohms
Series 8 I/O User's Guide
Honeywell
145ohms
+24
R28 through
R43
R500
April 2017