177
F3CALFL
TC/RTD FTA 3 calibration failure.
Diagnostic check:
Cause:
Solution:
178
F4CALFL
TC/RTD FTA 4 calibration failure.
Diagnostic check:
Cause:
Solution:
179
OPENWIRE
Open wire / sensor detected.
Diagnostic check:
Cause:
Solution:
180
DOVRCRNT
Digital Output channel detected a short circuit or over current situation.
Diagnostic check:
Cause:
Solution:
R500
April 2017
Check FTA calibration
TC/RTD FTA 3 calibration failure.
Recalibrate the FTA. This soft failure is introduced in Series 8.
Check FTA calibration
TC/RTD FTA 4 calibration failure.
Recalibrate the FTA. This soft failure is introduced in Series 8.
Check the field wiring and IOTA connections.
Open wire / sensor detected.
Check the field wiring and IOTA connections.
Check the field wiring and IOTA connections.
Digital Output channel detected a short circuit or over current
situation.
Check the field wiring and IOTA connections.
Series 8 I/O User's Guide
Honeywell
13. Series 8 I/O Alarms and Failures
13.2. Reviewing IOM soft failures
285