Ftamsmch; Vzero-Fl; Badrjval - Honeywell Series 8 I/O User Manual

Table of Contents

Advertisement

Diagnostic check:
Cause:
Solution:
31

FTAMSMCH

TC/RTD FTA type mismatch with channel configuration.
Diagnostic check:
Cause:
Solution:
32

VZERO-FL

Zero reference voltage out of range in Analog Input and Analog Output IOMs
Diagnostic check:
Cause:
Solution:
33

BADRJVAL

Reference junction value bad
Diagnostic check:
Cause:
Solution:
R500
April 2017
IOM diagnostic circuit failure.
IOM diagnostic circuit failure.
For Analog Input IOM, "noise" on the input may cause this
error.
Reset the IOM. If reset does not clear the error, replace the
appropriate IOM.
For Analog Input IOM, check for "noise" on the input.
Check channel block configuration.
TC/RTD FTA type mismatch with channel configuration.
Reconfigure the channel block or replace the FTA.
Zero reference failure.
Zero reference voltage out of range in Analog Input and
Analog Output IOMs
Replace the IOM.
Reference junction value bad
Series 8 I/O User's Guide
Honeywell
13. Series 8 I/O Alarms and Failures
13.2. Reviewing IOM soft failures
273