5.18 Configuring HART Configuration tab - Channel block

Configuring modules - HART Configuration tab

The following configuration information pertains to the HART Configuration tab for all
Series 8 I/O Analog Input and Analog Output modules.
The parameter HALARMENABLE is added to HART configuration tab in the channel
block and:
is enabled by default
in addition, can be changed from monitoring side, irrespective of the channel point
execution state of the IOM module state.
ATTENTION
When HALARMENABLE is disabled
Note: This parameter affects only the HART alarm / event behavior. The LED
device status in the HART device status tab is not impacted by the state of
HALARMENABLE.
Prerequisites
Control Builder is running
A Series 8 I/O control module was created
Considerations
All illustrations used in the procedure are for example purposes only.
The following is an example of an Analog Input Channel Block, Configuration form -
HART Configuration tab.
R500
April 2017
5.18. Configuring HART Configuration tab - Channel block
all the existing HART events / alarms from that channel block are
disabled
and further generation of the HART alarms / events are terminated
Series 8 I/O User's Guide
Honeywell
5. Series 8 I/O Configuration Form Reference
141