5. Series 8 I/O Configuration Form Reference
5.1. Overview
A. If the IOTA is redundant, perform the following steps depending on the IOM type.
For Analog and Digital Input Modules, perform the following steps.
Step
1
From Control Builder Monitoring View, for each loaded Input Channel, set PV
Source option (PVSRCOPT) to ALL.
2
From Control Builder Monitoring View, for each loaded Input Channel, set PV
Source (PVSOURCE) to MAN.
3
From Control Builder Monitoring View, select the IOM and perform an Upload
operation.
4
From Control Builder Monitoring View, select the IOM and perform an Update
to Project.
5
From Control Builder Project View, select the IOM and enable Redundancy
using the checkbox for This IOM is redundant (REDOPT) parameter.
6
From Control Builder Project View, select the IOM and perform a Load.
7
Ensure the IOM state is in Run.
8
If the channels were not selected to activate during the load operation, then
Activate them.
9
From Control Builder Monitoring View, for each loaded Input Channel, set PV
Source option (PVSRCOPT) to ONLYAUTO.
10
From Control Builder Monitoring View, select IOM and perform an Upload
operation to ensure ERDB Monitor database matches current configuration in
IO module.
11
From Control Builder Monitoring View, select IOM and perform an Update to
Project operation to ensure ERDB Project database matches Monitor
database.
For Analog and Digital Output Modules, perform the following steps.
Step
1
From Control Builder Monitoring View, select the IOM and perform an Upload
operation to ensure ERDB Monitor database matches current configuration in
106
ATTENTION
PV Source (PVSOURCE) automatically goes to AUTO.
Series 8 I/O User's Guide
Honeywell
Action
Action
R500
April 2017