6.3

Adding an IOC block to a Control Module

Using the Project tab drag and drop

When an IOM block is created in the Project tab, all of its associated IOC blocks are also
created. Clicking the + (plus sign) for the IOM expands the tree down to the IOC level.
You can drag and drop the IOC blocks into Control Modules. The Series 8 I/O IOC block
parameters can then be wired to other blocks in the same manner as existing Experion
function blocks.
Prerequisites
Control Builder is running
Controller was created, CM was created, IOM was added and assigned to an
IOLINK
To add an IOC to a Control Module by dragging and dropping from the Project tab,
perform the following steps.
Step
1
Click the + (plus sign) to expand the IO in the Project tab.
You can also select the tag name in the following methods.
Select library mode and type the initial characters of a tag name.
Use the Search Option toolbar.
a)
b)
R500
April 2017
Type the initial few characters of a tag name in the Search Option
toolbar. A list of all matching tag names appears.
Select the tag name and click
Series 8 I/O User's Guide
Honeywell
6. Series 8 I/O Configuration
6.3. Adding an IOC block to a Control Module
Action
161