Specifications - Altronix ACMCB220 Series Installation Manual

Access power controllers with power supplies, 12vdc or 24vdc 4/6/10 amp, ptc protected outputs
Hide thumbs Also See for ACMCB220 Series:
Table of Contents

Advertisement

These units distribute and switch power to access control systems and accessories. They convert a 220VAC 50/60Hz input
into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. These power outputs can be converted
to dry form "C" contacts. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an
Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control
hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-
Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trig-
ger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
Altronix
Model Number
AL400ACMCB220
AL600ACMCB220
AL1012ACMCB220
AL1024ACMCB220
• Power supply input options:
a) One (1) common power input for ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs (external power supply is required).
(current is determined by the power supply connected, not to exceed a maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
• Eight (8) independently controlled outputs Fail-Safe and/or Fail-Secure power outputs.
• Eight (8) auxiliary power outputs (unswitched) (outputs are rated 2.0 amp).
• ACM8CB board main fuse is rated at 10 amp.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is triggered (form "C" contact rated @ 1 amp 28VDC).
• Green LED indicates when FACP disconnect is triggered.
• Filtered and electronically regulated outputs (built-in power supply).
• Built-in charger for sealed lead acid or gel type batteries.
• AL400XB2V, AL600XB220 and AL1012XB220 (Power Supply Board) maximum charge current 0.7 amp.
AL1024XB220 (Power Supply Board) maximum charge current 3.6 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Thermal and short circuit protection with auto reset.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact).
• Battery fail and battery presence supervision (form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
Enclosure dimensions: 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm).
- 2 -
ACMCB220 Series Configuration Reference Chart:
4 amp
3 amp
8 2.0 amp 1.2 amp
6 amp
6 amp
8 2.0 amp 1.8 amp
10 amp
- - - - - - - - -
8 2.0 amp 1.6 amp
- - - - - - - - -
10 amp 8 2.0 amp 2.4 amp
Overview:
5A/250V
5A/250V
5A/250V
5A/250V

Specifications:

15A/32V
- - - - - - - - -
15A/32V
15A/32V
ACMCB220 series