Altronix ACMCB220 Series Installation Manual page 7

Access power controllers with power supplies, 12vdc or 24vdc 4/6/10 amp, ptc protected outputs
Hide thumbs Also See for ACMCB220 Series:
Table of Contents

Advertisement

Power Supply Board
Terminal
Function/Description
Legend
L, N
Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral.
AL400ACMCB220 - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board.
AL600ACMCB220 - 12VDC/24VDC @ 6 amp to ACM8CB board.
+ DC –
AL1012ACMCB220 - 12VDC @ 10 amp to ACM8CB board.
AL1024ACMCB220 - 24VDC @ 10 amp to ACM8CB board.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay
AC FAIL
normally energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is
NC, C, NO
reported within 1 minute of event. To delay reporting of up to 6 hrs.,
cut "AC delay" jumper and reset power to unit.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when
DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes.
BAT FAIL
Battery reconnection is reported within 1 minute.
NC, C, NO
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACM),
24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACM).
Stand-by battery connections. AL400XB2V, AL600XB220 and AL1012XB220
+ BAT –
(Power Supply Board) maximum charge current is 0.7 amp. AL1024XB220
(Power Supply Board) maximum charge current is 3.6 amp.
ACM8 Access Power Controller
Terminal Legend
– Power +
– Control +
TRIGGER
INPUT 1- INPUT 8
IN, GND
OUTPUT 1-OUTPUT 8
NC, C, NO, COM
FACP INTERFACE
T, + INPUT –
FACP INTERFACE
NC, C, NO
ACMCB220 series
Terminal Identification Tables:
Function/Description
12VDC or 24VDC input from power supply board.
These terminals can be connected to a separate power-limited, UL Listed power supply to
provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed).
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir's, etc.).
12 to 24 volts AC/DC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO become form "C" 5 amp 24VAC/VDC rated dry outputs when fuses are
removed. Contacts shown in a non-triggered state.
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (Fig. 4 through 8, pg. 8).
Form "C" relay contact rated @ 1 amp 28VDC for alarm reporting.
(This output has not been evaluated by UL).
- 7 -