Positioning Strap Retainers And Straps - Siemens SITRANS FSS200 Installation Manual

Ultrasonic clamp-on sensors
Table of Contents

Advertisement

Additional Installation Instructions
B.4 Hi Precision mount
Figure B-45
B.4.4.2

Positioning strap retainers and straps

Installation procedure
Straps should be cut to length and installed with strap retainers on the pipe.
1. Roughly position the strap retainers on the horizontal plane of the pipe with the strap
fastener located at the top of pipe.
2. Using the provided Mylar material, make a template by wrapping the Mylar strip around
the pipe and overlap the ends.
Figure B-46
3. Tape the ends together. Mark the Mylar template where the ends overlap with a marker.
4. Remove the template from the pipe.
5. Align the mark with the other end of the Mylar strip and then fold the Mylar strip keeping
the ends aligned.
6. Using a marker, mark the fold crease.
130
Hi Precision mount Direct mode Dual enclosure (for minimum index spacing)
Overlap edge
Mark (or fold) exactly at halfway point
Finding the halfway distance
Spacing guide
Circumference
Installation Manual, 08/2017, A5E36255466-AC
FSS200 clamp-on sensors