Commissioning
5.3.4 Changing Parameter Settings
Quick access to change parameter settings
1.
To enter the Quick Menu, press [Menu] until the
indicator in the display is located at Quick Menu.
2.
Press [
motor set-up, or changes made, then press [OK].
3.
Press [
in the Quick Menu.
4.
Press [OK] to select a parameter.
5
5
5.
Press [
setting.
6.
Press [►] to shift digit when a decimal parameter
is in the editing state.
7.
Press [OK] to accept the change.
8.
Press either [Back] twice to enter "Status", or
press [Menu] once to enter "Main Menu".
The Main Menu accesses all parameters
1.
Press [Menu] until the indicator in the display is
located at "Main Menu".
2.
Press [
groups.
3.
Press [OK] to select a parameter group.
4.
Press [
in the specific group.
5.
Press [OK] to select the parameter.
6.
Press [
Changes Made
1.
Press [Menu] until the indicator in the display is
located at "Quick Menus".
2.
Press [
3.
Press [OK] to select 05 Changes Made.
•
Changes Made lists all parameters changed from
default settings
•
The list shows only parameters which have been
changed in the current edit-setup.
•
Parameters which have been reset to default
values are not listed.
•
The message 'Empty' indicates that no
parameters have been changed.
28
Operating Instructions
▲
▼
] [
] to select wizard, closed loop set-up,
▲
▼
] [
] to browse through the parameters
▲
▼
] [
] to change the value of a parameter
▲
▼
] [
] to browse through the parameter
▲
▼
] [
] to browse through the parameters
▲
▼
] [
] to set/change the parameter value.
▲
▼
] [
] to browse through the quick menus.
Danfoss A/S © Rev. 06/2014 All rights reserved.
5.3.5 Thermistor Set-up
Set 1-90 Motor Thermal Protection to [1] Thermistor warning
or [2] Thermistor trip. For details refer to VLT
FCP 106 and FCM 106 Programming Guide.
®
DriveMotor
MG03L202